Troubleshooting a low-pressure alarm in industrial chillers requires a systematic approach to identify the root cause without overlooking critical factors. Here’s a step-by-step guide:
Lockout/Tagout: Secure the chiller before inspection.
Check Secondary Alarms: Verify if other alarms (e.g., low temp, flow) are active.
Review BAS History: Identify when the alarm triggered relative to load changes or startups.
| Cause | Diagnostic Action | Key Evidence |
|---|---|---|
| Refrigerant Undercharge | Check sight glass for bubbles; compare suction pressure to design specs. | Low superheat; subcooling >10°F below normal. |
| Leak in Evaporator | Inspect tubes for corrosion/oil stains; use UV dye or electronic detector. | Oil traces in water; pressure drops during isolation test. |
| Restriction | Check ΔP across filter drier/expansion valve. | Frost on TXV/Liq. line; high subcooling. |
| Purge Unit Overworking | Monitor purge cycle frequency; check for non-condensables. | High discharge pressure; air in refrigerant sample. |
| Cause | Diagnostic Action | Key Evidence |
|---|---|---|
| Low Chilled Water Flow | Verify pump operation; check strainers for clogs; measure ΔP across evaporator. | ΔT >12°F; flow meter readings < design. |
| Setpoint Error | Confirm chilled water temp setpoint hasn’t drifted. | BAS shows illogically low target temp (e.g., <38°F). |
| Load Drop | Review process demand; check valve positions. | Actual load < 30% capacity; low return water temp. |
| Cause | Diagnostic Action | Key Evidence |
|---|---|---|
| Faulty Sensor | Calibrate pressure transducer; compare with gauge readings. | Sensor reading vs. manual gauge mismatch. |
| Expansion Valve Fault | Check valve signal; listen for hunting/chattering. | No response to manual override; erratic superheat. |
| Compressor Wear | Inspect oil for metal flakes; check bearing clearance. | High vibration; amperage fluctuations. |
Isolate the Section
Close service valves to separate evaporator from the circuit. Monitor pressure for drops.
Test Water Flow
Measure evaporator ΔP:
Normal: 8–12 PSI
Low flow: ΔP < 5 PSI → Check pumps/strainers.
Check Refrigerant Charge
Record subcooling/superheat:
Low charge: Low suction pressure + high superheat (>15°F).
Restriction: Low suction pressure + high subcooling (>20°F).
Inspect Purge Unit
If cycling >5 times/hour: Likely air ingress or leak.
Validate Controls
Bypass BAS temporarily; manually command valves/sensors.
Evaporator Freezing (risk of tube rupture):
→ Symptoms: Suction line frost; water outlet temp < 36°F.
Oil Foaming (compressor damage):
→ Symptoms: Oil sump level rising; erratic pressure.
Non-Condensables >2%:
→ Symptoms: Head pressure spike after restart.
Low Flow: Clean strainers; balance water system.
Leak: Repair tubes (epoxy/plug) or replace bundle.
Undercharge: Recover, fix leak, evacuate, recharge.
Faulty TXV: Replace valve/strainer.
Sensor Error: Recalibrate or replace.
Annual Leak Checks: Helium testing (sensitive to 0.1 oz/year leaks).
Water Treatment: Prevent tube fouling/corrosion.
Real-Time Monitoring: Install pressure transducers with cloud alerts.
Training: Teach operators to spot early signs (e.g., gradual pressure drop over days).
If suction pressure remains low after basic fixes.
For brazing repairs on pressurized vessels.
If oil analysis shows contamination (acid/metals).